Applications and Features
l Apply high accuracy MEMS sensor and digital technologies, can measure positive, negative or differential pressure
l It can measure system pressure of fan, blower, filter, furnace draft and orifice plate and can apply to various clean room, biological safety cabinet, clean bench, ducts collection, medical or pharmaceutical machine, etc.
l Multiple ranges, outputs, engineering units selectable
l Suitable for surface, panel or flush mount
l No moving parts, no vibration, ultra-thin design (only 33mm)
l State of art housing, big screen LCD display, accuracy up to ±1%FS
l Key function: zero calibration, engineering unit switching, response time setting, range / signal calibration, etc.
Specifications
Medium: Non-combustible, non-corrosive air, insensitive to moisture, dust, condensation and oil
Medium Temp.: 0~60°C
Work Environment: -20~70°C
Temp. Compensation: 0~50°C
Work Pressure: overload 10xFS(≤1kPa)/8xFS(≥1kPa)
burst 20xFS(≤1kPa)/10xFS(≥1kPa)
Size: 115mm diameter opening/33mm thick for flush mount
Connection: 1/8” ID tubing, two pairs (on left side and back)
Display: 4 bits large LCD, 68x30.5mm with figure H 22.6mm, and engineering unit
Output: 0-10V (3 wires) & 4-20mA (2 wires)
Output Load: ≤500Ω (current), ≥2kΩ (voltage)
Digital Output: RS485/Modbus(9600-n-8-1)
Electrical connection: screw terminals
Accuracy: ±1.0%FS (±2%FS@25Pa)
Stability: ±0.5%FS /Year
Thermal effect: <0.05%FS/°C (Zero), <0.08%FS/°C (FS)
Response time: 0.5-30s
Power: 9-28VAC, 9~35VDC
Key: 3 touch buttons
Material: fire retardant ABS+PC(UL94V-0)
Protection: IP65
Weight: 320g
Approval: CE
Accessory: Standard accessories include 1002(5mm ID PVC tube 2m) and A-S0 (including 3 brackets and screws). Options are A-S1, A-S2 and A-S7-X. They can be used for surface, panel or flush mount and should be ordered separately. See details in Accessories.
Models
model | D2T |
|
| Digital display differential pressure transmitter |
range |
| x |
| See Ranges |
output |
|
| 1 | 0-10V DC (3~wires) |
|
| 2 | 4-20mA (2~wires) |
|
| 8 | RS485/Modbus |
1.The standard electrical connection is cable from the back of enclosure. If select screw terminals instead, add suffix -T after the Model No.
2.The standard front cover is matte black. If select matte white instead, add suffix -W after the Model No.
Ranges
Code | UNIT & Range & Display Resolution |
Pa | Pa | kPa | in w.c. | mm w.c. | mbar |
0 | 0-25 | 25.0 | 0.025 | 0.100 | 2.50 | 0.250 |
1 | 0-60 | 60.0 | 0.060 | 0.250 | 6.00 | 0.600 |
2 | 0-125 | 125.0 | 0.125 | 0.500 | 12.00 | 1.250 |
3 | 0-250 | 250.0 | 0.250 | 1.000 | 25.00 | 2.500 |
4 | 0-500 | 500.0 | 0.500 | 2.000 | 50.00 | 5.000 |
5 | 0-1000 | 1000 | 1.000 | 4.000 | 100.0 | 10.00 |
6 | 0-2500 | 2500 | 2.500 | 10.00 | 250.0 | 25.00 |
7 | 0-5000 | 5000 | 5.000 | 20.00 | 500.0 | 50.00 |
8 | 0-10000 | 10000 | 10.000 | 40.00 | 1000.0 | 100.00 |
1. 5 engineering units can be set by keys and the related LCD logo will be on.
2. For zero center models, add “Z” at the end of the model. For example, D2T1xZ, means calibrated range is -30-0-30Pa. Only ranges 1~6 have this selection.