Applications& Features
l Designed for flush mount, measure and display environment differential pressure such as cleanrooms in electronics or pharmaceutical plants, hospital and laboratories, etc.
l 316L front panel, PMMA window, flat surface, no dust stays, good for all detergents, sanitizers and bactericides
l Strong EMI capability, compatible with the EMI requirements of EN61326-1 for industrial equipment
l DP17 has large LCD and DP17M has 3.2” TFT color LCD
l High performance sensor, 100% interchangeable sensor without re-calibration,1 channel 4~20mA output
l Compatible to any DDC/PLC/SCADA or other data collect and control systems
Specifications
Different pressure sensor:
Display:
(1) DP17: 4 bits LCD (with backlight), display area 47x27mm, with word H 16mm and unit H 2mm
(2) DP17M: 3.2" TFT color LCD (320×240), high light, can be set to DP value and real-time curves
Display panel material: PMMA
Resolution: 0.1Pa(or 0.001 in wc/mbar, 0.01mm wc etc., switchable)
Update time: <1s
Power Supply: 16~28VAC/19~35VDC
Consumption: DP17< 1 VA, DP17M< 2 VA
Analog outputs:1×4~20mA(3/4 wires), RL<500Ω; over voltage and reverse polarity protection; accuracy as low as 0.1%FS(0.5%FS accuracy)/ 0.3%FS(1.0%FS accuracy)
Communication(DP17M): 1xRS485/Modbus RTU, R/W 9600 baud rate; can set brightness, display setting functions and parameters calibration, etc. May set terminal resistance
Data(DP17M): Support data curve trend display
Keys(DP17M): can set display mode/parameter, brightness, unit and communication parameters, etc.
Process connection: Built-in DP sensor: 2 conical nozzles on back, ? 5 mm tube connection
Zero set: zero button / key
Terminals: max ?1.5mm2
Work Environment: 0~50°C, 0~95%RH (no cond.)
Storage Environment: -10~70°C
Front panel material: 316L stainless steel, 1.5mm thick
Back housing parts: fire retardant ABS+PC(UL94V-0)
Protection: front panel IP65
Weight: about 450g
Approval: CE, meet EN61326-1 for industrial equipment
Models
Measuring Ranges
1. Set the 5 engineering units by button keys and the related LCD indicator will be on.
2. For zero center models, add “Z” at the end of the model. Only ranges 1~5 have this selection.
For example, DP171**Z, means the range is -30-0-30Pa.